EMI AMERICA SERIESMULTI-ZONE LIMITED RANGE HEAT PUMP CONDENSING UNITS P/N# 240006458 Rev. 1.0 [01/07]Enviromaster International LLC5780 Success Dr.Rom
www.enviromaster.com10Multi-zone Heat Pump Condensing Units9. Once certain of a good evacuation and leak free joints, back-seat the valves (count
www.enviromaster.com11Multi-zone Heat Pump Condensing UnitsCIRCUIT CAPACITYEVAPORATOR PAIRINGLINE CHG/FTLINE LENGTHLINE ADJUSTFACTORY CHARGE SYSTEM TO
www.enviromaster.com12Multi-zone Heat Pump Condensing UnitsFIELD CHARGING
www.enviromaster.com13Multi-zone Heat Pump Condensing UnitsFIELD CHARGING
www.enviromaster.com14Multi-zone Heat Pump Condensing UnitsSTARTING THE UNIT• Before starting the unit in cool weather, power the system 24 hours
www.enviromaster.com15Multi-zone Heat Pump Condensing UnitsSTART-UP AND TROUBLESHOOTING TEST PROCEDURE The Test Unit Performance Data sheet below
www.enviromaster.com16Multi-zone Heat Pump Condensing UnitsMULTI-ZONE CONDENSER SEQUENCE OF OPERATIONEMI America Series multi-zone heat pump condenser
www.enviromaster.com17Multi-zone Heat Pump Condensing UnitsMULTI-ZONE CONDENSER SEQUENCE OF OPERATIONWhen the outdoor temperature falls below 35°F, co
www.enviromaster.com18Multi-zone Heat Pump Condensing UnitsS2HA DIMENSIONS AND SPECIFICATIONSNOTE: All EMI products are subject to ongoing development
www.enviromaster.com19Multi-zone Heat Pump Condensing UnitsS2HA SYSTEM PERFORMANCES2HA / WLHA SYSTEM PERFORMANCEMODEL COOLING HEATINGS2HA(Outdoor)Indo
Phone: 1-800-228-9364Fax: 1-800-232-93645780 Success Drive, Rome, NY 13440
www.enviromaster.com3Multi-zone Heat Pump Condensing UnitsINSTALLATION, OPERATION AND MAINTENANCE MANUALEMI AMERICA SERIES MULTI-ZONE HEAT PUMP CONDEN
www.enviromaster.com4Multi-zone Heat Pump Condensing UnitsEMI AMERICA SERIES MULTI-ZONE HEAT PUMP CONDENSING UNITSCONTROLS AND COMPONENTS(FACTORY INST
www.enviromaster.com5Multi-zone Heat Pump Condensing UnitsINSTALLATION INSTRUCTIONS1. Loosen the screws on left and right sides of the front panel. (D
www.enviromaster.com6Multi-zone Heat Pump Condensing UnitsELECTRICAL WIRING INSTALLATION SECTION3. Use only HACR type breakers or time delay fuse
www.enviromaster.com7Multi-zone Heat Pump Condensing Units8. Check wiring diagram for the re-quired number of low voltage wires to be run betwee
www.enviromaster.com8Multi-zone Heat Pump Condensing UnitsThe system will support refrigerant runs to the inside unit of up to 100' equivalent fe
www.enviromaster.com9Multi-zone Heat Pump Condensing Units8. Evacuate line to 500 microns or less to ensure all moisture has been removed and there ar